●Brief Description
Circuit breaker is used for making and breaking normal current, fault current and switching lines to realize the control and protection of power system.
LW10B-550/CYT SF6 circuit breaker, with the advantages of strong current-carrying capacity, excellent breaking performance, high reliability and so on, is equipped with CYT hydraulic mechanism, which adopts modular design, built-in hydraulic pipes, so as to realize no external pipe, no leakage.
● Main Features
1 High insulation level, excellent breaking performance of the interrupter.
2 Equipped with independently-developed CYT hydraulic mechanism, all hydraulic pipes built in, no leakage, good mechanical reliability.
3 Adopting imported control valve, with stable performance and anti-slow-opening function in case of pressure loss.
4 The component parts are highly interchangeable with other products of PINGGAO, experienced manufacturing technology, easy to maintain on site.
● Technical Parameters
Specifications
|
Unit
|
Value
|
Rated voltage
|
kV
|
550
|
Rated current
|
A
|
4000
|
Rated frequency
|
Hz
|
50/60
|
Rated short-time withstand current (r.m.s)
|
kA
|
63
|
Rated peak withstand current
|
kA
|
160
|
1min power frequency withstand voltage (r.m.s)
|
To earth/Between phases
|
kV
|
740
|
Across isolating distance
|
kV
|
740(+315)
|
Lightning impulse withstand voltage (peak)
|
To earth/Between phases
|
kV
|
1675
|
Across isolating distance
|
kV
|
1675(+450)
|
Rated operating impulse withstand voltage (peak)
|
To earth/Between phases
|
kV
|
1300
|
Across isolating distance
|
kV
|
1175(+450)
|
Rated SF6 gas pressure(20℃)
|
MPa
|
0.6
|
Rated SF6 annual leakage
|
%
|
≤0.5
|